CH12A | CABLES
Signalling
CONTENTS
- Introduction
- Signalling Cables
- Telecommunication Cables
- Power Cables
- Selection of Cable Type
- Methods of Termination
- Cable Routes
- Cable Construction
- Electrical Properties
- Cable Testing
- Data Cable
- Fiber Cables
-
INTRODUCTION
Railway signalling now involves a wide range of equipment and techniques to transmit information, ranging from simple d.c. to carrier and data transmission. Associated with these is an equally wide range of interconnecting cables. Some are peculiar to railway signalling. Others are generally produced for telecommunications or general electrical purposes and have found applications within railway signalling.
Refer Article Signalling Cable Standards on Rail Factor for a comprehensive list of cable standards, user of this article shall make effort to cross refer their current local guideline/standard in this regard.
2. SIGNALLING CABLES
Most lineside signalling circuits are d.c. or mains frequency a.c. Voltages are low, typically 24 - 120 volts. In some cases point machine can be 3 phase ,415/400 Volts ,3 wire system.
Cables designed for conveying d.c. or low frequencies are generally far simpler than those for a.c. use. This is because the transmission of d.c. is far less demanding on the type and dimensions of the insulating materials and also on the construction of the cable. Under d.c. conditions the voltage drop along the cable conductor is the product of the current flowing and the resistance of the conductor. As long as the insulation material and its thickness is chosen such that its resistance is very high then it will have little or no effect on the voltage drop along the conductor.
Although the electrical characteristics of most signalling cables will be similar, cable construction will vary according to the environment in which the cable is to be installed.
The most common variants are:-
2.1 Internal wiring
This is usually flexible (stranded conductor) for easy installation along relay racks ,cable frame ,interlocking cabinets and cable ducts. The cable will generally be installed in a controlled environment so the sheath will not have to withstand such great changes in temperature, humidity and mechanical stresses as those installed outside.
Many countries now have quite stringent requirements for the sheath material to satisfy fire regulations, the objective being to avoid emission of harmful gases in the event of a fire. Many existing internal cables have a PVC sheath. EVA (Ethylene Vinyl Acetate, otherwise known as Cross Linked Polyethylene) is often preferred now as it generally satisfies fire regulations.
Some railways insist to use double sheathed insulation. Requirements for emission of smoke /and hazardous gas can be referred to IEC 61034-1/-2 and IEC60754-1 respectively. Similarly, IEC 60332-1 & IEC 60332-3 for flame test on Single wire and bunched wires respectively. UL1581 is an American Standard for electrical wires. Standard Size of wires are defined by AWG (American Wire Gauge)/European Or British Standards.
Similar requirements exist for cables in tunnels and EVA sheathed cables are also used on underground railways.
Internal cables are generally required as multicore cables (e.g. wiring between racks) and single core (individual circuits in interlockings and locations). Annealed Copper wires are used for electrical conductor compliant to IEC 60228(Australian AS/NZS 1574 & section 1&2 of 1125 )
2.2 Lineside Cables
Although these may carry similar circuits to the internal cables, they must withstand a more hostile environment. Typically, they will be installed in lineside troughs or buried and will be subject to changes in temperature and humidity, often lying-in waterlogged ground. Often UV Rays, oil, rodent and vermin will also be a problem.
Individual conductors are insulated by an ethylene propylene rubber (EPR) compound/ while the outer sheath is polychloroprene (PCP) to give an oil resistant cable which will also withstand abrasion. If the cable requirement ask for UV Protection, Low Smoke Zero Halogen, Flame/Fire Retardant, carbon/iron/ wash plant liquid protection, outer sheath shall be selected accordingly . HDPE (High Density Polyethylene) cross linked polythene cover majority of such requirements.
Most cables are multicore, to carry many separate signalling circuits. A single conductor will normally be adequate as the cable will not be subject to significant vibration once installed. Power cables are of similar construction but generally consist of two cores (for d.c. or single phase a.c. distribution and will generally have a stranded conductor due to the cross-section required.
Some railways favour some form of armoured sheath (e.g. steel wire) for added mechanical protection.
2.3 On-track Cables
Trackside electrical equipment is generally connected by cables across or under the ballast. Such cables must be strong and capable of withstanding considerable vibration. British Railway uses a flexible, multi-strand cable. Materials and construction are as for the lineside cables above, but the sheath is thicker, and the conductor is composed of a larger number of smaller strands (50/0.50mm).
Again, many railways prefer an armoured cable but this can also present problems with earth faults where the risk of damage to the cable is high.
3.TELECOMMUNICATION CABLES
Under a.c. conditions the inductance and capacitance of a cable can have a considerable bearing on the voltage drop and these factors become of major importance as the frequency increases.
The capacitance of a cable pair or conductor will depend on the type and thickness of the insulation material. For a given material the thickness required for ac. transmission will generally be greater than for d.c. transmission.
Suitable insulation materials for a.c. cables are dry air, paper and polythene. P.V.C. and rubber are not considered to be satisfactory, except in the case of low frequency cables such as 50Hz power.
With multicore cables there is the additional problem of interference in one circuit due to the current in a neighboring circuit, commonly called "Crosstalk". The degree of crosstalk which may be encountered can depend on a number of different factors e.g.
a) The frequency of the disturbing signal e. crosstalk increases with frequency (square waveforms, because of their high harmonic content are particularly troublesome).
b) The magnitude of the current flowing in the disturbing i.e. crosstalk increases with the current.
c) The position of the conductors in the cable relative to each
To satisfy the latter problem, cables are manufactured with cores twisted together to form pairs, and adjacent pairs may be twisted at different rates. A circuit should always utilise the two conductors of a pair for out and return. Common returns should not be used in such cables. The effect of twisting the conductors together in such a fashion is that cancellation of any induced voltage occurs across any load terminated at the ends: of the cable pair.
Often cables are made up in multiples of quads instead of pairs. In such cases a pair is formed by utilising the diametrically opposite cores. The resultant cable is smaller in diameter than the equivalent multi-pair cable, since there is less wasted space within the cable.
With the use of very high frequencies on carrier circuits and for broad bandwidth applications such as closed-circuit television, the problems of crosstalk and attenuation increase with frequency. Eventually, twisted pair cables become unsatisfactory. Coaxial cable, effectively a cable pair consisting of a central conductor surrounded by and insulated from an outer metallic sheath, is employed. The fields created by the high frequency signals are contained in the cylindrical space between the inner and outer conductors, thus alleviating the crosstalk problem. A larger spacing between conductors also reduces the high frequency attenuation.
4. POWER CABLES
For both signalling and telecommunications applications it is necessary to distribute power to the lineside. For most purposes this is best distributed as a.c. and transformed and/or rectified locally to the equipment served. A wide range of power cables is manufactured to supply the electrical industry, and these are generally employed within signalling and telecommunications systems. The sheath and/or insulation material may have to be modified to suit the specifications for signalling cable.
As most power distribution is single phase, 2-core power cables are generally used. The conductors may be stranded copper or solid aluminium.
5. SELECTION OF CABLE TYPE
5.1 Lineside Signalling Circuits
Signalling circuits will be taken to mean d.c. or mains frequency a.c. circuits between an interlocking and a lineside location (or between locations) to convey signalling information. They are normally laid in main cable routes and may be very numerous in areas of complex signalling.
Cables for signalling circuits normally utilise conductors with only one strand, as mechanical strength is not of major importance. Typical cross sectional area is 0.5 to 2.5mm2. To economize on installation costs, a smaller number of cables with a higher number of cores is preferred.
5.2 Tail Cables
On-track cables (tail cables) to lineside equipment (e.g. signal heads, point machines etc.) from relay rooms or location cupboards must withstand physical damage and vibration. The
B.R. standard cable has 50 strands to give it flexibility and a heavy-duty sheath for protection. The following sizes are commonly used:
5.3 Power Distribution
Standard industrial sizes of 2-core power cable are used. The size of the conductors will depend on the power loading and the consequent voltage drop along the line. For most types of signalling equipment, a voltage drop of 10% is usually the maximum acceptable. It is therefore important to perform an estimate of power consumption of all equipment before deciding upon the size of cable to install. Allowance should be made for possible future additions to the electrical load. Renewal of power cables at a later stage can be expensive.
5.4 Internal Relay Room/Location Wiring
Due to the diverse termination points of internal circuits, the only means of installing internal circuits is to use individual wires. Cables may be useful for wiring between racks or between different rooms/floors of a building to simplify installation by allowing factory pre- wiring.
Alternatively, armoured (e.g. steel wire) cable could be used. This has fallen in popularity in recent years due to cost, difficulty of handling and difficulty in performing a satisfactory repair in the event of damage.
6 . METHODS OF TERMINATION
All cables and wires must be terminated to connect on to other equipment. Each individual conductor in the cable will normally be terminated, even though some cores may be spare. In addition to terminating the individual cores the cable sheath is often clamped to a fixed bar in the location or equipment room. This is to avoid the weight of the cable placing a strain on the individual terminations which could lead to breakage of the conductors.
The following are the most widely used forms of termination: -
6.1 Crimped Termination
This method is mainly used for stranded cables. It is unsuitable for small cross-section single conductors as it weakens the conductor mechanically. It is a mechanical method which involves compressing a metal termination on to the wire.
Various types of crimped connector are available:-
a) A "ring" type connector to fit over a screw terminal. This is secured by nuts and washers.
b) "Spade" type connectors which can be inserted into equipment terminals without the need to completely remove nuts and washers.
c) A special type of spade connector for use in BR930 relay bases. These are simply inserted into the relay base. The crimps are constructed so as to spring apart slightly and lock the wire in position. A special tool is required to extract this type of connector
d) "Shoelace " type connectors which can be inserted into equipment terminals without the need to completely remove nuts and washers.
There are terminals available capable of inserting wires without the need of ferrules. Its recommended to use ferrules for multi stranded wires, however single wire cores can be inserted without a ferrule.
For all types of crimped connection, it is important to choose the correct size to suit the terminal, the size of conductor and the size of insulation. Its also important to ensure the terminal can withstand the current carrying capacity of the wire.
6.2 Screw Terminals
These are used in conjunction with crimped terminations or to directly terminate the conductors of solid cored cables. The cable is held tightly by a screw and/or nuts and washers to provide mechanical strength and electrical continuity.
Where screw terminals are used, it is common to provide disconnection links to enable portions of the circuit to be isolated.
6.3 Plug Couplers
Where modular equipment requires to be unplugged it is common to connect all wiring to a plug coupler. Wires may be soldered or wire-wrapped for security. This allows very quick disconnection and reconnection and avoids the need to check and/or test the wiring when a module is replaced.
Plug couplers are often electrically or mechanically coded to ensure that they are only connected to the correct equipment.
7. CABLE ROUTES
A safe route must be determined for the cables, both within buildings and externally. Within buildings, suitable ducts may be provided as part of the building or the equipment racking.
If the cable route is shared with other than signalling cables, it must be ascertained that there is no hazard from electrical interference.
Outside buildings there are several methods of cable installation used. These are described below.
7.1 Troughing
Troughing is laid on the surface. It is usually inset into the ground for stability and the safety of staff walking along the track. Cable installation is simple. The lids are removed, the cables placed in the trough and the lids replaced. Two types are now in common use:-
a) Ground Level Sectional Concrete Troughing.
b) Ground Level Plastic Troughing.
Plastic troughing is easier to handle but requires more accuracy in installation. Lids must be clipped on rather than being held in place by their own weight.
7.2 Ducts
The following types of cable duct are in general use:-
a) Earthenware duct
b) Thick wall Rigid V.C. duct
c) Thin wall V.C. duct. This duct must be laid in concrete
d) Asbestos Cement duct - not generally available but has been used in the past in large quantities.
e) Steel duct
f) Flexible plastic pipe - this is corrugated along its length to allow the pipe to bend
A common problem with all ducts is that over a long period of time they tend to accumulate debris which is either washed or blown into them. After a long period of time has elapsed, this may make further cable installation more difficult.
7.3 Cable Racks or Trays
Slotted steel or plastic trays may be fixed to lineside structures, retaining walls etc. Cables may be fixed to this using plastic cable ties. The cable route is easily accessible for installation purposes but is also exposed to the environment and may be unsatisfactory in areas where vandalism is a problem.
A similar method is to use cable hangers - hooks on to which the cable is placed and held in position by its own weight. This method is particularly useful in tunnels where there is little risk of vandalism and clearances are limited.
7.4 Buried Cables
Provided the cable sheath is suitable cables may be buried direct in the ground. This avoids the cost of providing an expensive cable route.
Cables are normally buried in one of two ways:-
a) Laid in a trench with protective tapes or tiles and backfilled.
b) Mole ploughed using a mechanical mole ploughing machine.
In both cases warning markers should be provided on the surface at regular intervals. Buried cables suffer from several problems:-
a) It is difficult to install further cables at a later stage without risk of damaging existing cables.
b) Cables are vulnerable to excavations by others as they are not visible. Cable markers may eventually become obscured.
c) Fault location and rectification is more difficult.
d) Over a long period, ground movements and the growth of tree roots etc. may stretch and damage the cables.
When specifying the type of cable installation, the engineer should take all costs, risks and benefits into account.
7.5 Aerial Cable
Where an existing pole route is in good condition, it may be economic to install aerial cable. Aerial cable is however vulnerable to damage (gunshot, falling branches etc.) and the effects of lightning.
Ordinary cable is unsuitable for aerial installation. Aerial cable has a steel strainer wire installed to provide the necessary tensile strength for hanging on poles.
7.6 Application
In general the application of the above methods are as follows:-
7.6.1 Track-side cable routes
Ground Level Concrete Troughing and Plastic Troughing is usually preferred where a large number of cables is required. Burying may be employed for small cable routes (i.e. single lines). Aerial cable could be considered if an existing pole route is still in good condition and the risk of damage or interference is low.
7.6.2 Under Track Crossings
Practices vary but in general steel or asbestos cement ducts are preferable because of their ability to withstand vertical impact. In some cases thick wall P.V.C. duct has been used. Ducts should be installed sufficiently far below the track to be clear of track maintenance equipment (tamping machines, ballast cleaners etc.).
7.6.3 Platform Routes
In general, platform routes should be provided with cable ducts and associated manholes for access to joints and pulling through of cables. Usually, it is more convenient to use earthenware ducts for platform routes.
Surface troughing or hangers along the platform edge may interfere with track maintenance.
7.6.4 Tunnels
The method used will depend upon the construction and cross section of the tunnel. It is often difficult to install a ground level route which will be clear of track maintenance machinery. Cable trays or hangers on the tunnel wall are therefore the most suitable.
It is of course possible to design new tunnels to accommodate a cable route. Whether this is best located on the tunnel wall or floor will be determined by the type of track and tunnel drainage requirements.
7.6.5 Tail Cables
Opinions vary on the best method. It is unlikely that there is a best method which suits both the signal engineer and the permanent way engineer. Cables may be simply laid across the top of the ballast. These are visible and easily removed and replaced. They are also vulnerable to damage by track maintenance and trailing objects on trains. Use of surface level ducts provides added protection but interferes with track maintenance. Placing the ducts below ballast level increases installation costs. Ducts can also become blocked with ballast and other debris. Surface cables secured to the top surface of the sleepers have greater protection than those laid loose across the ballast. This method may not always be acceptable to the track engineer. Tracks laid on concrete sleeper can use hard hats to cover the cable where hard hats are fastened on the concrete.
8. CABLE CONSTRUCTION
A vast range of cables is now available. it is only possible to cover some of the main features of modem signaling cables in this section. There are many other cables widely in use for different application including control voltage to a Point Machine. Refer Figure 2 for the construction of a modern quad cable with Water Resistant property. Even though below section is based on Quad Cable Construction, we use this opportunity to discuss other alternative options available for armour, screen, internal & external sheath and the conductor insulation. Selection of PVC materials (XLPE -Cross Linked Polyethylene, LDPE -Low Density Polyethylene HDPE -High Density Polyethylene) and the addictive included for UV, Pest, Carbon /Iron /Copper/Mineral Dust, Acid /Salt, Industrial Cleaning solution shall be selected according to the operators need and the type of environment for the intended application. It is signal engineers’ responsibility to ensure that cable will not fail and select the property in case operator doesn’t specify detailed requirement.
8.1 Conductor Materials
Copper is the most widely used conductor material due to its very low resistance and excellent mechanical properties. It is also available in sufficient quantities at an acceptable price.
The copper is manufactured as wire of a consistent cross-section by repeatedly drawing the copper through holes in dies of reducing cross-section until the desired size is reached. As this process tends to harden the copper wire, it is usually annealed to restore its ductile properties. Annealed copper wires are complied to EN60811-203 /IEC 60228 .Refer RailFactor Article “Standard for Signalling cables “ as well for more details.
Where rubber insulations are employed, the copper is generally coated with tin to prevent a chemical reaction between them causing corrosion of the copper and a change in the mechanical properties of the rubber.
Where a large cross-section is required, aluminium may be used in place of copper (e.g. for power cables). Although Aluminium is more resistive, it is lighter and cheaper and has greater mechanical strength. Aluminium cables generally employ a solid conductor and are therefore more rigid than the copper equivalent.
8.2 Insulating Materials
Each core of a cable must be insulated from all others and must therefore be surrounded by an insulating material throughout its length.
Signalling cables use thermoplastic (P.V.C. or Polyethylene) or elastomeric (natural rubber or polychloroprene (P.C.P.)) insulations. The addition of P.C.P. to rubber improves its resistance to weathering. In very wet conditions, however, it has a tendency to absorb water over a long period of time. This will adversely affect its electrical characteristics.
With telecommunications cables, the capacitance between cores becomes significant with a.c. signals. Dry air is the best insulator but impractical for cable construction. In older cables paper was widely_ used. This effectively consisted of a mixture of organic fibres and a large proportion of air spaces. As paper insulation is no longer used, polyethylene ie: HDPE (High Density Polyethylene-Solid) insulation is common these days with Low Smoke, Zero halogen property especially in the tunneled application.
8.3 Formation of Conductors
Quad formation of conductors are the most recent trend for multicore cables .They are constructed in 1 Quad (4 Core ) ,3Quad (12 Core) ,4 Quad ( 16 Core ) , 5Quad (20Core ), 7Quad( 28Core) and 10Quad ( 40 core) .Each quad is arranged in the form of a Star (Diamond) and twisted together to get the best electrical property in terms of mutual Capacitance ( <45nF/Km) and Electromagnetic Compatibility compared to other formation which makes higher mutual capacitance .Lightly twisted pair formation is also available for better Electro Magnetic Compatibility. German DB(DB416.0115-Standard) defined Quad cable is popular for CBTC /ETCS application. Quads are helically stranded in concentric layers and cables more than 7Quad include two extra conductors with perforated insulation for surveillance. Signal Engineer shall select the compatible cable with respect to their signalling solution.
8.4 Core Identification
Cores are identified in a number of ways, for a DB defined Quad Cable as shown in Figure 2 on light brown conductors black bracelets are printed in different combination .Eg: Two black circles printed together and repeated on fixed length apart ,One circle printed and repeated on certain length etc .
As a Designer I am not a big fan of such identification as its confusing for the technicians for the first time. Methods of identification can be classified into 5.
a) Coloured Tape wrapped around each core
b) Coloured Insulation (Especially for Signalling Application Power Cables)
c) Numbered Tape
d) Numbering Printed on the insulation.
e) Identification concentric rings (as mentioned above on DB defined Quad Cable)
When numbering is used care must be taken to avoid confusion between 6 and 9. The easiest method is to write the number (six or nine) as well as or instead of the numerals.
Various systems of colour coding are used depending on the size, type and manufacturer of the cable. In a paired cable only one conductor may be colour coded.
The numbering of cable cores/pairs always starts from one at the centre and increases towards the outside of the cable. Each end of the cable is identified - the A end is the end at which the numbering of each layer runs in a clockwise direction, the opposite end is the B (or Z) end.
8.5 Core Wrapping, Screen, Inner Jacket, Swellable Tapes & Armour
Plastic tapes are overlapped around cores which collectively hold all the cores together, on top of it, a copolymer coated aluminium tapes are wrapped. Tinned copper wire of 0.5 mm. run along the cable making in contact with the aluminium tape. This arrangement provides the functional earthing (EMC) option for the cable. This continuity wire needs to be earthed along with the armour for earthing the induced current generated due to parallelism (double sided for AC Traction line and singe sided for DC Traction). This arrangement is protected with Black coloured Zero Halogen Low Smoke compound PVC Inner jacket. Steel Tape armour is taped around the inner jacket.
Swellable water blocking tapes are wrapped around the Inner jacket and Steel armour to avoid longitudinal water penetration. This arrangement along with inner and outer sheath is making the cable compliant to moisture barrier requirement per BS-EN 50288-1, EN 50288-7 or equivalent, water immersion test complying to IEC 61156-1. This construction is ensured to pass the Transversal water tightness and armour long water tightness test according to EN50289-4-2/A and water absorption for conductor insulation and outer jacket according to EN60811-402.
8.5.1 Types of Armour
Armour provides additional mechanical heavy-duty protection, such as crushing, and resistance from pest such as rodent penetrating into inner conductor. Some cables will have nylon wrapping beneath outer sheath to protect from Termites and steel tape armour for rodent protection. Metallic armour not only provide mechanical protection it can also offer EMC protection but dose not replace the need for screen but lines less than 25kV can consider avoid screen under specific conditions.
1) Steel Tape Armour
Steel Tape armour is sandwiched between water blocking tapes for DB cable. These are used for buried cables. According to American Railway Engineering and Maintenance of way Association (AREMA) states that tape armouring provide high degree of shielding protection than shield wires.
2) Steel Wire Armour
Steel wire surround lead sheath for some cable design and are used for buried cable. This will surround the braided sheath and such sheath are used for high frequency emc protection
3) Corrugated armour
Corrugated steel /copper surround the cable lengthwise beneath the outer sheath which is used for lines less than 25kv .This is mainly used in Optical Fiber Cable for optimum flexibility and recommended to replace with Fibers Reinforced Plastic (FRP) for electrified territory more than 25kV due to chance for high induced voltage.
8.5.2 Types of Shield/Screens
Screening /shielding is used for reducing the effect of electromagnetic interference (EMI) or electrical noise which can disrupt the transmission performance in some environments. This noise may be because of external
interference from other electrical equipment or because of interference generated within the cable from adjacent pairs (cross talk).
1) Aluminium /polyester tape with a tinned copper drain wire
DB 416.0115-Standard Quad Cable referenced in Figure 2 have aluminium foil with attached tin plated copper wire .
2) Copper /polyester tape with a tinned copper drain wire
This solution can provide better screening effect compared to aluminium foil.
3) Bare copper braid
This is good for electromagnetic interference when the cable is subject to movements
4) Tinned copper braid
Good for electromagnetic interference in presence of corrosive atmosphere or high temperature
8.6 Outer Jacket
In addition to insulating individual cores, the entire cable must be contained within a sheath for both mechanical strength and environmental protection.
Cross Linked Polyethylene (High Density Polyethylene Otherwise known as HDPE) are the most widely used. Low Density Polyethylene-LDPE) are also used depends on area of usage. Some older cables used lead, but its expense and associated health risks have led to its disuse.
The choice of sheath material should consider the environment in which the cable will be used. Factors such as moisture, exposure to light and heat, the presence of oils and solvents, presence of carbon/iron dust, Train washing plant solutions, temperature, water immersion (IPX7) /submersion (IPX8) and the required level of resistance.
In nutshell outer jacket is one of the most important elements for mechanical protection from external damages such as chemical (oxidation acid, oil), Mechanical (Abrasion), Environmental (Heat, Sun exposure, moisture, water), Fire exposure etc. Thermoplastic or Thermoset polymers are widely used where Thermoset have excellent properties against threats.
8.6.1 Ingress Level- Mechanical Properties.
Mechanical shock severity shall be shared with the cable supplier whether its Low (Energy shock of 0.2 J, mainly for household installation hence not applicable) or Medium (Energy shock of 2J-standard industrial application) or high severity (Energy shock -5J)
8.6.2 Ingress Level- UV Resistance.
Designer shall share the UV intensity requirement to the cable supplier based on the regional severity and exposure levels whether its Low (AN1 – Intensity ≤500 W/m²) or Medium (<500 W/m² intensity ≤700 W/m²) or High (<700 W/m² intensity ≤1120 W/m²). Refer Rail Factor Article “Standards for Signalling Cables” for more details.
8.6.3 Ingress Level- Water
8.6.3.1 Water Environment
8.6.3.2 Water Penetration
The factor defines the water penetration in cables and to prevent the entry and migration of moisture or water throughout the cable. Water ingress can happen through Radial due to sheath damage and in this case, water enters in the cable by permeation through protective layers or due to any mechanical damage. Once water enter the cable, it travels longitudinally through out of the cables core. Where as longitudinal penetration moisture or water enters inside cables core due to ineffective capping or poor cable joint /termination .Please note water proofing and water absorption tests are different .There are no specific test for longitudinal water penetration for power cables .Radial water penetration test shall only be applied .Separate water penetration barrier are applied below the armour (or metallic screen layer ) and along conductor .Refer cable construction above in Figure 2
8.6.3.3 Moisture Protection
Resistance offered by the jacket and the additional chemical used are ensuring the protection. However, the material with highest degree of water resistance is often not flame resistant, hence a tradeoff must be made between these two contradictory requirements. Choice of sheath material, make use of chemical moisture barrier and water blocking tapes can protect the cables from moisture.
8.6.4 Flame & Fire
8.6.4.1 Low Smoke Zero Halogen (LSOH)
This is the property of cable to emit very low smoke and zero halogen and ensuring low corrosivity and Toxicity. Even though normal PVC cable ensure better mechanical and electrical properties, its poor in fire retardancy, corrosivity and low smoke capability.
8.6.4.2 Smoke Density
Smoke can prevent fire fighters’ visibility and evacuation, especially in tunnel, work areas, control room and public areas.
8.6.4.3 Flame Retardant
Flame Retardant property is vital, during a fire flame spread shall be retarded to limit to a confined area thus eliminating fire propagation.
8.6.4.4 Fire Retardant
Property which when ignited do not produce flammable volatile products in required amount to give rise to a secondary outbreak of fire.
8.6.4.5 Fire Resistant
Fire resistant cables are designed to maintain circuit integrity of emergency services during fire. Please note that Fire resistant cables are super expensive and normally considered for very vital cables (Eg; Fire cabinet ,depend on contractual requirement .Please note that Fire Resistant and fire retardant are different property and fire resistant is more stringent requirement.
The individual conductors are wrapped with a layer of fire resisting mica/glass tape which prevents phase to phase and phase to earth contact even after the insulation has been burnt away. The fire-resistant cables exhibit same performance even under fire with water spray or mechanical shock situation.
8.6.5 Pest Resistant
Depends on the intended area of the project ,there could be various threats such as ants, termite ,rodents , squirrels ,wood peckers ,other birds ,beetle and larva where cable contact with any plants to mention some .Various chemical compounds added on to the sheath ,depends on pest chemical and armours are protecting the cable .It may not be practical to have armoured cable for indoor application due to flexibility issue and outdoor environment have more threats .
9. ELECTRICAL PROPERTIES SIGNALLING CABLES
9.1 Voltage Rating of Cable
Signalling control cables are normally rated for 600v/1000V. Voltage range classification for LV, HV, AC & DC according to IEC 60038 are as shown in Table 3
Maximum for High Voltage for IEEE is 35kV and in some countries its 45kV, which is country specific.
Refer Table 4 for maximum permitted voltage Vs Rated voltage.
9.2  Resistance of Cable
This is the resistance of wire which increases with distance and normally included in the cable data sheet from the supplier. Its measured Ω/kM @ 50Hz (or 60Hz) and 20°C. This is the main parameter to calculate the voltage drop of cable. Voltage received at the end gear shall not be less than 10% of the source voltage. This means when you feed 130V from the SER, signal at the track side should at least get 117V. Cable conductor size shall be selected based on voltage drop calculation and shall cross check with field gear data sheet that the 10% voltage drop allowed will still fall in the minimum required voltage
Important Note: Signal Engineer shall ensure that the resistance value (Ω/kM) provided by the supplier in the data sheet is loop resistance or wire resistance. Loop resistance means it’s the value for two conductors. While calculating voltage drop, number of loops used for the respective circuit and its distance shall be used.
9.3 Reactance of Cable
This is defined in Ω/kM @50Hz (or 60Hz). This is important parameter for MV cables which need to be asked from the supplier but for LV, designer can define the allowed limit for LV
9.4 Capacitance of Cable
Measured in µF /KM which is mandatory parameter for MV cable and shall be requested from supplier. As mentioned above Quad formation have less than 40µF /KM. Lower the capacitance better the cable property.
9.5 Maximum Short Circuit Current (Conductor and Screen)
Maxum short circuit current in kA for conductor and screens for 1.0 seconds and 0.5 seconds respectively shall be requested and obtained from supplier.
10 CABLE TESTING
It is not the purpose of this article to give detailed instructions on the procedures for testing and maintenance of different types of cable. However, the general principles of cable testing are described here.
In general, whenever a cable is installed, repaired, re-terminated or jointed and at regular intervals during the life of the cable, tests must be made to ensure that: -
a) Each core is continuous and of the correct resistance. A rise in the resistance of a core could indicate a potential fault.
b) Each core is insulated from all other cores. It is normal for the insulation resistance to fall slightly during the life of a cable. Serious deterioration must, however, be detected before it causes any safety hazard.
c) Each core must be adequately insulated from earth. Unwanted connections to earth are a potential danger to all signalling circuits and must be avoided.
Where the cable has a metallic sheath, the insulation tests must include the sheath. Where the sheath is earthed and/or bonded for reasons of safety or noise immunity, the continuity of the sheath is also important.
The continuity tests may be made using a suitable digital or analogue multi-meter set up to measure resistance. All tests will require the cooperation of persons at each end of the cable. A telephone circuit between the ends (using the cable to be tested if convenient) is essential to carry out an efficient test. The simplest method is to put a loop between one conductor and each other conductor in turn at one end of the cable. The loop resistance is measured at the other end using the meter. Any variation between individual readings (and changes since the previous test) should be investigated and resolved before the cable enters (or re-enters) service.
Insulation and earth tests should use a suitably rated insulation tester (1000-volt Megger or similar for signalling cables). Tests should be performed between each core and each other core in turn. The acceptable value of resistance for a cable will depend on the circuits connected through it. However, as a general guide, a new signalling cable should give readings better than 10MΩ (when terminated). Readings less than 1MΩ could potentially be dangerous and require urgent investigation.
The earth test may initially be carried out between earth and all cores connected in parallel. Only if this test is unsatisfactory need individual cores be tested to earth.
Although a new cable is always completely tested before being brought into use, a complete test of a working cable is not always practical without serious disruption. In this case, routine tests are often carried out on a sample of cable cores (spare cores if available). Previous readings should be retained for comparison.
11. DATA CABLES
Ethernet cables falls under this category. They are classified into different category Cat 1 to Cat 9, whereas Cat 1-4 are not suitable for modern day rail application and above Cat7 is not yet came into application while preparing the article. Refer Table 4 for category classification.
Data cables with twisted pairs have different construction depends on the purpose, cable shall be selected. Refer Table 6 for various construction.
12. Fiber Cables
Although many signalling applications must use metallic cables, the availability and cost of fiber optic cables is rapidly improving. Instead of electrical signals, they transmit information by passing light signals along the length of a glass fiber. Internal reflection contains the light signal within the fiber.
Although not specifically employed in conventional signalling systems, fiber optic technology has the following advantages and necessary for modern communication-based train control system: -
a) An extremely high capacity and bandwidth.
b) Immunity from all types of electrical It is therefore of great use for communications purposes on electrified lines.
Conventional jointing techniques are not applicable to glass fiber cables. Instead, the two ends must be cut squarely, butted up to each other and fused together by the application of heat. This is a very precise operation as any irregularities in the fiber will cause attenuation of the signal.
Much of the work of jointing fiber cables can now be done automatically by sophisticated (and usually very expensive) fusion splicers. The action of cutting the two ends squarely, aligning them for a parallel joint and fusing for the correct period of time is largely automatic.
Even with the high degree of automation, fusion splicing is not always 100% satisfactory each time. It is therefore usual to provide additional spare fiber at the joint. This must be accommodated within the joint closure.
Category cables have limitation to transfer data more than 100meter, Fiber has significance in this case.
There are two types of fibers:
- Single Mode: Long Distance Application
- Multi-Mode: Short Distance Application
Single mode Fiber must be complied to G652-D type as per ITU-T standard and multimode with IEC 60793-2-10
There are two types of construction
- Loose Tubes used in cable concrete trough, direct buried and other harsh environment
- Micro Tubes for less harsh environment
The END
NOTE :- Please comment if you wish to include Cable Voltage Drop Calculation , Stanadard conductor sizes and a sample cable plan
To continue reading Register Now or Login